      Simplify design, save space and reduce costs for you
      JB-QBC-BS10 Automatic marine fire alarm & Water-based cabin fire extinguishing control system
      BS10 Automatic Fire alarm controller
      Integrated entire ship cabin fire alarm and water mist fire extinguishing control functions in one
      The main performance index
      Meets the requirements of MSC.1/Circ.1387 in Chapter 9 of the FSS Code. It can be used for fixed local water-based fire extinguishing systems in Category A machinery spaces.
      Wiring system
      Two-wire ring-distributed, non-polarity
      Capacity
      127 × 8(Loop) = 1016 Maximum addressing capacity
      Transmission distance
      ≤ 1500 meters
      Quadratic Programming
      In addition to display the alarm address, the alarm point can display the alarm location described by textual
      APOLLO bus device 126*4 circuit
      =504 Maximum addressing capacity
      LCD screen with multi-information on the same screen
      Chinese and English bilingual conversion
      Two kinds of installation options
      Wall mounted, Flush mounted
      BS10 Fire Detector
      Intelligent algorithm to determine accurate and reliable fire
      Address card indicator: convenient for inspectors to directly obtain the detector's address number
      BS10-system fire detectors adopt digital value transmission and floating threshold value processing technology, and their basic difference from normal fire detectors is that they have no fixed alarm threshold, i.e. when the environment changes or a detector is contaminated by the environment, its internal intelligent algorithm will automatically identify and adjust the alarm threshold to adapt to the new environment and condition, so the function of threshold drift compensation enables every fire detector to has a sensitivity relatively constant to external environment.
      BS10 Infrared Flame Detector
      Dual-band Infrared Ray + Dynamic Flash Frequency Identification
      Effectively prevent false alarm caused by non-combustion
      Detecting a fan-shaped conical area with a 120-degree field of view, the centerline distance can reach 25 meters.
      BSKY+APOLLO, Model of Sino-foreign Cooperation
      The BS10 controller has been rigorously tested by Apollo in the United Kingdom and is authorized to mate with Apollo‘s XP95 and Discovery series of fire detectors.
      ◆ System features
      • Meets both requirements of Europe MED on fire alarm and MSC.1/Circ.1387 in Chapter 9 of the FSS Code. It can be used for fixed local water-based fire extinguishing systems in Category A machinery spaces
      • Maximum addressing capacity:127 × 8(Loop) = 1016
      • Intelligence algorithms are used in controller and detectors to reduce the mis-alarm event
      • Selective detector isolation function for easy system maintenance
      • Address card indicator, convenient for inspectors to directly obtain the detector's address number
      • The monitored location can be directly described by textual alternative address number display, which is more intuitive
      • LCD screen with multi-information on the same screen, Chinese, English bilingual conversion
      • Two kinds of installation options, wall mounted and flush mounted
      ◆ Technical specifications
      JB-QBC-BS10 Fire alarm controller
      Main power supply AC 110/220V (+10%~-15%) ,50HZ/60HZ
      Emergency power supply AC 110/220V (+10%~-15%) ,50HZ/60HZ
      Backup DC power for ships DC 24V(+30%~-25%)
      Internal battery DC 24V,2.2AH
      Power consumption Monitoring status: ≤10W, Alarm status: ≤12W
      Standard EN-54/2,4
      Number of loop boards Two at most
      Capacity of each loop board 4 circular loops with 128 alarm points each
      Alarm time of manual alarm ≤5s
      Alarm time of detecto ≤10s
      Loop max. Communication distance ≤1500m
      Communication distance between detector and ≤1500m
      Way of wiring BS10-series alarm point – 2 wiring system, non--polar
      BS10-series module – 4 wiring system
      Fire protection zone Max. 16 Fire protection zone,they can be set to any separate loop
      Output of the device Dry contact output,contact capacity 1A,DC30V:
         — Fire output 6
         — Fire delay output 1
         — PA output 1
         — Fault output 4
         — Power fault output 2
         — System fault output 2
      Power supply to the output,DC24V,max. current 1A:
         — Fire delay output 1
         — Door hold output 1
      Alarm input from other system 2 sets of passive input contacts
      Way of installation wall type / flush mounting type
      Fire alarm history records Max 999 instances
      Other history records Max 999 instances
      Working temperature 5℃~55℃
      Relative humidity (Non-condensing) Max.95%
      Installation dimensions 525×146×515(L×W×H)mm3
      Weight 22Kg
      Degrees of protection IP44

      JB-QBC-BS10 Fire alarm controller
      Main power supply AC 110/220V (+10%~-15%) ,50HZ/60HZ
      Emergency power supply AC 110/220V (+10%~-15%) ,50HZ/60HZ
      Backup DC power for ships DC 24V(+30%~-25%)
      Internal battery DC 24V,2.2AH
      Power consumption Monitoring status: ≤10W, Alarm status: ≤12W
      Standard EN-54/2,4
      Number of loop boards Two at most
      Capacity of each loop board 4 circular loops with 128 alarm points each
      Alarm time of manual alarm ≤5s
      Alarm time of detecto ≤10s
      Loop max. Communication distance ≤1500m
      Communication distance between detector and ≤1500m
      Way of wiring BS10-series alarm point – 2 wiring system, non--polar
      BS10-series module – 4 wiring system
      Fire protection zone Max. 16 Fire protection zone,they can be set to any separate loop
      Output of the device Dry contact output,contact capacity 1A,DC30V:
         — Fire output 6
         — Fire delay output 1
         — PA output 1
         — Fault output 4
         — Power fault output 2
         — System fault output 2
      Power supply to the output,DC24V,max. current 1A:
         — Fire delay output 1
         — Door hold output 1
      Alarm input from other system 2 sets of passive input contacts
      Way of installation wall type / flush mounting type
      Fire alarm history records Max 999 instances
      Other history records Max 999 instances
      Working temperature 5℃~55℃
      Relative humidity (Non-condensing) Max.95%
      Installation dimensions 525×146×515(L×W×H)mm3
      Weight 22Kg
      Degrees of protection IP44
      JB-QBC-BS10R Fire indication panel
      Main power supply DC 24V(±10%)
      Power consumption Monitoring status: ≤ 1.5W; Alarm status: ≤ 2.4W
      Communication distance between detector and ≤1500M
      Working temperature 5℃~55℃
      Relative humidity (Non-condensing) Max.95%
      Way of installation wall type / flush mounting type
      Installation dimensions 245×102×176(L×W×H)mm3
      Weight 22Kg
      Degrees of protection IP44

      JB-QBC-BS10R Fire indication panel
      Main power supply DC 24V(±10%)
      Power consumption Monitoring status: ≤ 1.5W; Alarm status: ≤ 2.4W
      Communication distance between detector and ≤1500M
      Working temperature 5℃~55℃
      Relative humidity (Non-condensing) Max.95%
      Way of installation wall type / flush mounting type
      Installation dimensions 245×102×176(L×W×H)mm3
      Weight 22Kg
      Degrees of protection IP44
       
      Type and name JTY-GD-BS10 Point-type photoelectric smoke detector JTW-ZD-BS10 Point-type heat fire detector J-SAP-BS10 Manual fire alarm button J-SAP-BS10WP Manual fire alarm button JTG-ZW-BS10 Point-type infrared flame detector
      Working voltage DC 18~26V DC 18~26V DC 18~26V DC 18~26V DC 18~30V
      Static power consumption ≤0.35W ≤0.35W ≤0.35W ≤0.35W ≤0.35W
      Alarm power consumption ≤1.5mA ≤1.5mA ≤1.5mA ≤1.5mA ≤1.5mA
      Working temperature -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃
      Relative humidity (Non-condensing) ≤95% ≤95% ≤95% ≤95% ≤95%
      Weight 0.26Kg 0.26Kg 0.1Kg 0.3Kg 1.9Kg
      Degrees of protection IP44 IP44 IP22 IP22 IP22

      Type and name JTY-GD-BS10 Point-type photoelectric smoke detector
      Working voltage DC 18~26V
      Static power consumption ≤0.35W
      Alarm power consumption ≤1.5mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.26Kg
      Degrees of protection IP44

      Type and name JTW-ZD-BS10 Point-type heat fire detector
      Working voltage DC 18~26V
      Static power consumption ≤0.35W
      Alarm power consumption ≤1.5mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.26Kg
      Degrees of protection IP44

      Type and name J-SAP-BS10 Manual fire alarm button
      Working voltage DC 18~26V
      Static power consumption ≤0.35W
      Alarm power consumption ≤1.5mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.1Kg
      Degrees of protection IP22

      Type and name J-SAP-BS10WP Manual fire alarm button
      Working voltage DC 18~26V
      Static power consumption ≤0.35W
      Alarm power consumption ≤1.5mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.3Kg
      Degrees of protection IP22

      Type and name JTG-ZW-BS10 Point-type infrared flame detector
      Working voltage DC 18~30V
      Static power consumption ≤0.35W
      Alarm power consumption ≤1.5mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 1.9Kg
      Degrees of protection IP22
       
      Type and name LIC-BS10 Line isolator DI-BS10 Cabin isolation unit IMC-BS10 Input module RMC-BS10 Input / Output module SMC-BS10 Audible and visual fire alarm
      Working voltage DC 18~26V DC 18~26V DC 18~26V DC 18~26V DC 18~26V
      Loop Static power consumption ≤0.78mA ≤0.38mA ≤0.5mA ≤0.38mA ≤1mA
      Loop Alarm power consumption ≤4.6mA ≤1.5mA ≤1.5mA ≤2.6mA ≤3mA
      24VStatic power consumption —— ≤1.2mA ≤18mA —— ≤18mA
      24VAlarm power consumption —— ≤10mA ≤45mA —— ≤45mA
      Working temperature -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃
      Relative humidity (Non-condensing) ≤95% ≤95% ≤95% ≤95% ≤95%
      Weight 0.2Kg 0.7Kg 0.7Kg 0.7Kg 0.7Kg
      Degrees of protection IP44 IP44 IP22 IP44 IP44

      Type and name LIC-BS10 Line isolator
      Working voltage DC 18~26V
      Loop Static power consumption ≤0.78mA
      Loop Alarm power consumption ≤4.6mA
      24VStatic power consumption ——
      24VAlarm power consumption ——
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.2Kg
      Degrees of protection IP44

      Type and name DI-BS10 Cabin isolation unit
      Working voltage DC 18~26V
      Loop Static power consumption ≤0.38mA
      Loop Alarm power consumption ≤1.5mA
      24VStatic power consumption ≤1.2mA
      24VAlarm power consumption ≤10mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.7Kg
      Degrees of protection IP44

      Type and name IMC-BS10 Input module
      Working voltage DC 18~26V
      Loop Static power consumption ≤0.5mA
      Loop Alarm power consumption ≤1.5mA
      24VStatic power consumption ≤18mA
      24VAlarm power consumption ≤45mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.7Kg
      Degrees of protection IP22

      Type and name RMC-BS10 Input / Output module
      Working voltage DC 18~26V
      Loop Static power consumption ≤0.38mA
      Loop Alarm power consumption ≤2.6mA
      24VStatic power consumption ——
      24VAlarm power consumption ——
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.7Kg
      Degrees of protection IP44

      Type and name SMC-BS10 Audible and visual fire alarm
      Working voltage DC 18~26V
      Loop Static power consumption ≤1mA
      Loop Alarm power consumption ≤3mA
      24VStatic power consumption ≤18mA
      24VAlarm power consumption ≤45mA
      Working temperature -25℃~70℃
      Relative humidity (Non-condensing) ≤95%
      Weight 0.7Kg
      Degrees of protection IP44
      ◆ Other Accessories
       
      Type and name DB-BS10 Detector base DBF-BS10 Detector water-proof base LIC-BS10 Detector isolating base SJX Junction box for manual call point AD-BS10 Address programme
      Function description Used with BS10 series smoke or heat detector together. Used with BS10 series smoke or heat detector and DB-BS10 detector base, in order to enhance their IP degree. Used with BS10 series smoke or heat detector, in order to isolate the wires if they are short. This junction box is used to fix the manual call point outside. Used to set the BS10 series bus-device's address and test their functions.
      Working temperature -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃ -25℃~70℃
      Dimensions Φ103X14 mm 140X128X41 mm Φ105X28 mm 87X87X32 mm 180X109X39 mm
      Weight 0.1Kg 0.2Kg 0.1Kg 0.1Kg 0.4Kg

      Type and name DB-BS10 Detector base
      Function description Used with BS10 series smoke or heat detector together.
      Working temperature -25℃~70℃
      Dimensions Φ103X14 mm
      Weight 0.1Kg

      Type and name DBF-BS10 Detector water-proof base
      Function description Used with BS10 series smoke or heat detector and DB-BS10 detector base, in order to enhance their IP degree.
      Working temperature -25℃~70℃
      Dimensions 140X128X41 mm
      Weight 0.2Kg

      Type and name LIC-BS10 Detector isolating base
      Function description Used with BS10 series smoke or heat detector, in order to isolate the wires if they are short.
      Working temperature -25℃~70℃
      Dimensions Φ105X28 mm
      Weight 0.1Kg

      Type and name SJX Junction box for manual call point
      Function description This junction box is used to fix the manual call point outside.
      Working temperature -25℃~70℃
      Dimensions 87X87X32 mm
      Weight 0.1Kg

      Type and name AD-BS10 Address programme
      Function description Used to set the BS10 series bus-device's address and test their functions.
      Working temperature -25℃~70℃
      Dimensions 180X109X39 mm
      Weight 0.4Kg